Calculate PoE++ Power Budgets After Cable and Splitter Loss

Calculate usable PoE++ watts after Ethernet cable loss and splitter conversion, then check the switch budget with a worked 12 V example.

Illustrated title card for the guide: Calculate PoE++ Power Budgets After Cable and Splitter Loss

To calculate usable PoE++ power, subtract the Ethernet cable loss from the watts supplied by the port, then multiply the watts at the splitter input by its conversion efficiency. Cap the result at the splitter’s DC output rating. If you start from the powered-device class budget, the cable allowance is already included. AOS-Switch 16.11 PoE class table · Analog Devices’ DC-DC efficiency guide · PLANET splitter specifications

Start with the power class the port grants

The switch or injector is the power sourcing equipment (PSE). The splitter is the powered device (PD) on the Ethernet link. The table shows the highest single-signature class for each IEEE 802.3bt type. Use the class granted by the source port for the connected splitter. AOS-Switch 16.11 PoE class table · Fluke Networks’ PoE installation guide

IEEE 802.3bt classAt the source portAt the splitter’s PoE input
Type 3, Class 660 W51 W
Type 4, Class 890 W71.3 W

Convert the splitter’s input watts to usable DC

Multiply the available input watts by the splitter’s efficiency as a decimal, using an efficiency figure for the intended input voltage and load. Apply the published output limits for the selected voltage. Divide the resulting DC watts by that voltage to get available amps, then compare them with the device’s required current. Analog Devices’ DC-DC efficiency guide · PLANET splitter specifications

You can also work backward from the load. Multiply the device’s required volts and amps, then divide by the splitter’s efficiency to get the required input watts. If the splitter publishes input consumption for that exact DC output, use that figure directly. Analog Devices’ DC-DC efficiency guide · PLANET splitter specifications

Estimate cable loss and voltage drop

For a balanced four-pair link, four equal conductors share the outward current and four share the return. Divide one conductor’s end-to-end resistance by four for each direction, then add the two directions. For an installed channel, include patch cords and connections in the resistance estimate. Fluke Networks’ PoE installation guide · Fluke Networks’ contact resistance guidance

Use the total PoE current, in amps, and the effective loop resistance, in ohms. If you know the port’s watts and voltage at the same operating point, divide those watts by that voltage to get the current. If you start from the load, divide the required input watts by the splitter’s minimum design voltage to estimate current at that voltage. Analog Devices’ DC-DC efficiency guide

  • Cable loss in watts = current² × loop resistance.
  • Voltage drop in volts = current × loop resistance.
  • Source watts required = splitter input watts + cable loss.
  • Source voltage required = splitter input voltage + voltage drop.

Worked example with a 12 V splitter

PLANET lists 65.6 W of consumption at full load for its IPOE-175S with a 12 V, 5 A output. That is 60 W out, or 5.6 W of splitter loss. The implied efficiency at that point is 60 W ÷ 65.6 W ≈ 91.5%. PLANET lists 52–56 V DC under its four-pair PoE power requirements. Use 52 V at the splitter as the design target for this example. PLANET splitter specifications · Analog Devices’ DC-DC efficiency guide

Assume a 50 m run of Belden 7965E bulk cable with balanced conductors. Belden lists a maximum DC resistance of 95 Ω/km per conductor. Belden 7965E specifications

QuantityCalculation
Effective loop resistance95 Ω/km × 0.05 km ÷ 2 = 2.375 Ω
Input current at the design voltage65.6 W ÷ 52 V ≈ 1.26 A
Cable loss(65.6 W ÷ 52 V)² × 2.375 Ω ≈ 3.8 W
Cable voltage drop(65.6 W ÷ 52 V) × 2.375 Ω ≈ 3.0 V
Required at the source for this estimate65.6 W + 3.8 W ≈ 69.4 W and 52 V + 3.0 V ≈ 55.0 V

PLANET lists the IPOE-175S as an IEEE 802.3bt Type 3 powered device. A Class 6 budget falls short of the splitter’s 65.6 W input requirement. For comparison, a hypothetical Class 8 powered device with the same input requirement would have enough watts in its class budget. For this cable estimate, the source also has to supply about 55.0 V at the design current to meet the selected splitter voltage. AOS-Switch 16.11 PoE class table · PLANET splitter specifications · Analog Devices’ DC-DC efficiency guide

Check the total switch budget

Subtract existing source-side port allocations from the switch’s total PoE budget. If 80 W remains and the switch needs to reserve 90 W for the next port, the allocation is 10 W over budget even if the example’s estimated draw is 69.4 W. Junos OS PoE guide for EX Series switches

Evidence and limits. The AOS-Switch 16.11 class table, Junos OS EX Series guide, Fluke Networks cabling guidance, Analog Devices equations, and Belden 7965E and PLANET IPOE-175S specifications were checked on November 27, 2026. The example is a steady-state calculation, and no hardware tests were performed.

Sources

  1. HPE Aruba Networking AOS-Switch 16.11 PoE class table
  2. Junos OS PoE guide for EX Series switches
  3. Analog Devices DC-DC efficiency and source resistance
  4. Fluke Networks PoE installation guide
  5. Fluke Networks DC contact resistance guidance
  6. Belden 7965E cable specifications
  7. PLANET IPOE-175S splitter specifications

More on the card